STC test — laboratory sound insulation testing to ASTM E90 and ISO 10140-2
An STC test measures how much airborne sound a building element stops. ALT tests full-size walls, doors, windows, partitions and barriers in a pair of decoupled reverberation rooms, and reports the result as STC to ASTM E413 and as Rw with C and Ctr to ISO 717-1 — for manufacturers, specifiers and contractors who need a number from a laboratory that has no stake in the product.
What is an STC test?
An STC test measures how much airborne sound a wall, door, window or partition blocks. The specimen is built into the aperture between two reverberation rooms, one room is driven with noise, and the level difference between the rooms is corrected for the absorption in the receiving room. That gives the transmission loss in each one-third-octave band. The band values are fitted to a reference contour under ASTM E413, and the single number that comes out is the Sound Transmission Class.
Higher is better. One extra STC point is roughly one decibel less sound through the element, so the difference between STC 35 and STC 50 is the difference between hearing a raised voice next door and hearing nothing at all. The ISO equivalent is Rw, the weighted sound reduction index, measured to ISO 10140-2 and rated to ISO 717-1. STC is fitted over sixteen bands from 125 to 4,000 Hz; Rw runs from 100 to 3,150 Hz.
Both are laboratory ratings of one element. Neither describes a finished building, and neither is a property of a material on its own — a 12 mm board scores differently depending on the studs, the cavity, the insulation and the seals it is built with. The assembly is what is tested, which is why the mounting description in the report matters as much as the number.
How an STC test is done at ALT
The specimen is built into the test aperture to the mounting condition your specification calls for, scanned with an acoustic camera to prove the perimeter is sealed, and only then measured. The measurement itself follows ASTM E90 and ISO 10140-2; the rating follows ASTM E413 and ISO 717-1. The whole sequence is carried out by the laboratory, not by the client or the installer.
- The specimen is built into the aperture between the source and receiving rooms, complete with frame and seals where it is a door set or a window set.
- The installed specimen is scanned with an acoustic camera to locate leaks at the perimeter before anything is measured.
- If the scan shows a path, the specimen is re-installed and re-scanned. The official measurement starts only once the mounting is sound.
- Pink noise is generated in the source room and the sound pressure level is averaged over fixed positions in both rooms.
- Reverberation time is measured in the receiving room so the result can be corrected for its absorption.
- Transmission loss is calculated for each one-third-octave band across the measured range.
- STC is fitted to ASTM E413 and Rw with C and Ctr to ISO 717-1, from the same set of band values.
- The report is issued with the band values, the curve, the mounting description and photographs of the installation as tested.
Every specimen is scanned before we measure
A gap of a millimetre where the specimen meets the test aperture can cost several decibels in the upper bands, and would understate what your product actually achieves. Before the official measurement we scan the installed specimen with an acoustic camera to confirm the mounting is sound. If it is not, we re-install and re-scan. Included as standard.
STC or Rw — which one do you need?
Use the one your specification names. Both rate airborne sound insulation from the same kind of laboratory test, but they are fitted over different frequency ranges under different rules, so the two numbers are close more often than not and interchangeable never. Where a product is sold into both markets it is cheaper to ask for both ratings from one test at the outset than to repeat the test later.
| STC | Rw | |
|---|---|---|
| Measurement standard | ASTM E90 | ISO 10140-2 |
| Rating standard | ASTM E413 | ISO 717-1 |
| Frequency range | 125–4,000 Hz | 100–3,150 Hz |
| Spectrum adaptation terms | None | C and Ctr reported alongside Rw |
| Usually named by | North American specifications and most international hotel brand standards | ISO-based and European specifications, and most Thai project specifications |
Rw and STC do not convert reliably between each other, and we do not publish a conversion. If a specification names one, test to that one.
Laboratory STC and what you will measure on site
A laboratory STC describes the element on its own, mounted without flanking paths. On site, sound also travels around the element — through junctions, floor and ceiling voids, service penetrations, ducts and the gaps left by other trades. The measured field rating is therefore lower, typically by five to ten points, and the gap is almost always workmanship rather than product.
Field ratings have their own names and their own standards: ASTC to ASTM E336, and DnT,w to ISO 16283-1. A laboratory STC of 50 does not entitle anyone to claim ASTC 50 in the finished building, and specifications that quote a laboratory number as an acceptance criterion on site are a common source of dispute.
ALT measures in the laboratory. We do not carry out field measurement in occupied or finished buildings, and we do not design, sell or supply the elements we test. If your project needs a site measurement we can tell you which standard to name and what to ask for, and you appoint the consultant of your own choosing.
What STC rating do you need?
There is no single right answer: the target comes from the specification, not from the laboratory. What follows is the scale most specifiers work from, in terms of what a person on the quiet side actually hears.
| STC | What is heard on the quiet side |
|---|---|
| 25 | Normal speech can be understood |
| 30 | Loud speech can be understood |
| 35 | Loud speech is audible but not intelligible |
| 40 | Loud speech is faint |
| 45 | Loud speech is inaudible |
| 50 and above | Most loud sounds are inaudible |
| Element | Typical STC |
|---|---|
| Hollow-core timber door | 20–25 |
| Single glazing | 27–30 |
| 100 mm concrete block, plastered both sides | 45–48 |
| Double-stud gypsum wall with cavity insulation | 55 and above |
Thai building law sets no general minimum STC for walls between rooms. In practice the requirement comes from the project specification, from hotel brand standards — commonly STC 50 to 55 between guest rooms — or from a green building scheme. Test to the figure your contract names, and have the mounting condition written into the scope before the specimen is built.
Building elements and products we test
- Doors and door sets — timber, steel, acoustic and fire-rated, tested as a complete set with frame and seals.
- Windows, glazing units and curtain wall panels — single, double and laminated glazing, fixed and openable.
- Partition systems — gypsum board on stud, blockwork, demountable and glazed office partitions.
- Facade and cladding panels, sandwich panels and metal composite systems.
- Acoustic barriers, enclosure panels and machine enclosure elements.
- Operable walls, access panels, service doors and other assemblies that have to be tested complete.
The specimen has to fill the test aperture and be built the way it is installed, including frame, seals and any perimeter detail that carries sound. The opening is a fixed size, so confirm it with us before anything is fabricated or shipped.
What you receive
- Sound reduction index R, or transmission loss, in one-third-octave bands — the underlying curve, not just the headline number.
- Sound Transmission Class (STC) to ASTM E413, from transmission loss measured to ASTM E90.
- Weighted sound reduction index Rw with the spectrum adaptation terms C and Ctr, to ISO 717-1.
- The plotted curve against the reference contour, so a reviewer can see where the assembly loses performance.
- A full description of the specimen and the mounting condition as tested, with photographs of the installation.
- A statement of traceability, the measurement uncertainty and the equipment used.
Scope status of this test
Airborne sound insulation testing is traceable to national standards and is outside ALT's ISO/IEC 17025 accredited scope, which covers calibration of sound level meters, sound calibrators and measurement microphones. We state this on every report rather than leave it to be discovered later.
Turnaround and how to book an STC test
Turnaround and logistics
- Typical turnaround
- About two weeks from receipt of a complete specimen and an agreed scope
- Urgent work
- An urgent route is available — tell us the date you are working to at enquiry, not after booking
- Before you ship
- Confirm specimen size, mounting and packing first — see sample requirements
- Report language
- Reports issued in English; correspondence in Thai or English
- How to start
- Send the testing requisition, or contact us by email, telephone or LINE @altbkk
Common questions about STC testing
What is STC testing?
An STC test measures how much airborne sound a wall, door, window or partition blocks, following ASTM E90 in a laboratory. The transmission loss in each one-third-octave band is converted into a single number, the Sound Transmission Class, using ASTM E413.
What does STC stand for?
Sound Transmission Class, the ASTM single-number rating of airborne sound insulation. The ISO equivalent is Rw, the weighted sound reduction index.
Should STC be high or low?
High. Each extra STC point is roughly one decibel less sound through the element. At STC 30 loud speech next door is understood; at STC 50 most loud sounds are inaudible.
Is an STC rating of 27 good?
Not for a wall between occupied rooms. STC 27 is the level of single glazing or a lightweight door, so loud speech is still understood through it. It can be acceptable for a window facing a quiet street, and it is well below the STC 50 to 55 that hotel brand standards usually ask for between guest rooms.
What is the difference between STC and Rw?
Both rate airborne sound insulation from the same kind of laboratory test. STC is fitted over 125 to 4,000 Hz under ASTM E413; Rw is fitted over 100 to 3,150 Hz under ISO 717-1 and is reported with the adaptation terms C and Ctr. The numbers are often close but are not interchangeable — use the one your specification names.
Why is the STC measured on site lower than the laboratory value?
The laboratory value describes the element alone. On site, sound also travels through flanking paths, junctions, service penetrations and gaps left by other trades, so the field rating — ASTC to ASTM E336 or DnT,w to ISO 16283-1 — is typically five to ten points lower. ALT measures in the laboratory and does not carry out field measurement.
What sample do I need to send for an STC test?
A full assembly that fills the test aperture, built the way it will be installed, including frame and seals for a door set or a window set. The opening is a fixed size, so confirm the dimensions with us before anything is fabricated or shipped — the sample requirements page and the testing requisition both ask for them.
How long does an STC test take, and is it accredited?
Typically about two weeks from receipt of a complete specimen, with an urgent route available if you tell us the date at enquiry. The measurement is traceable to national standards and sits outside ALT's ISO/IEC 17025 accredited scope, which covers calibration of sound level meters, sound calibrators and measurement microphones.
Last updated: 2026-10-14